Search Results (394 CVEs found)

CVE Vendors Products Updated CVSS v3.1
CVE-2025-9368 1 Rockwellautomation 1 432es-ig3 Series A 2026-04-15 N/A
A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device.
CVE-2025-9042 1 Rockwellautomation 1 Flex 5000 Io 2026-04-15 N/A
A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.
CVE-2025-11085 1 Rockwellautomation 1 Factorytalk 2026-04-15 N/A
A security issue exists within DataMosaix™ Private Cloud allowing for Persistent XSS. This vulnerability can result in the execution of malicious JavaScript, allowing for account takeover, credential theft, or redirection to a malicious website.
CVE-2025-7693 1 Rockwellautomation 1 Micro800 2026-04-15 N/A
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
CVE-2025-11743 1 Rockwellautomation 1 Compactlogix 5370 2026-04-15 N/A
A denial-of-service security issue in the affected product. The security issue occurs when a malformed CIP forward open message is sent. This could result in a major nonrecoverable fault a restart is required to recover.
CVE-2025-13823 1 Rockwellautomation 3 Micro820, Micro850, Micro870 2026-04-15 N/A
A security issue was found in the IPv6 stack in the Micro850 and Micro870 controllers when the controllers received multiple malformed packets during fuzzing. The controllers will go into recoverable fault with fault code 0xFE60. To recover the controller, clear the fault.
CVE-2025-7773 1 Rockwellautomation 1 Armorblock 5000 Io 2026-04-15 N/A
A security issue exists within the 5032 16pt Digital Configurable module’s web server. The web server’s session number increments at an interval that correlates to the last two consecutive sign in session interval, making it predictable.
CVE-2025-7973 1 Rockwellautomation 1 Factorytalk View 2026-04-15 N/A
A security issue exists in FactoryTalk ViewPoint version 14.0 or below due to improper handling of MSI repair operations. During a repair, attackers can hijack the cscript.exe console window, which runs with SYSTEM privileges. This can be exploited to spawn an elevated command prompt, enabling full privilege escalation.
CVE-2024-7567 1 Rockwellautomation 2 Micro850 Firmware, Micro870 Firmware 2026-04-15 N/A
A denial-of-service vulnerability exists via the CIP/Modbus port in the Rockwell Automation Micro850/870 (2080 -L50E/2080 -L70E). If exploited, the CIP/Modbus communication may be disrupted for short duration.
CVE-2025-9036 1 Rockwellautomation 1 Factorytalk Action Manager 2026-04-15 N/A
A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection.
CVE-2024-6079 1 Rockwellautomation 1 Emulate3d 2026-04-15 N/A
A vulnerability exists in the Rockwell Automation Emulate3D™, which could be leveraged to execute a DLL Hijacking attack. The application loads shared libraries, which are readable and writable by any user. If exploited, a malicious user could leverage a malicious dll and perform a remote code execution attack.
CVE-2024-9412 1 Rockwellautomation 1 Verve Asset Manager 2026-04-15 N/A
An improper authorization vulnerability exists in the Rockwell Automation affected products that could allow an unauthorized user to sign in. While removal of all role mappings is unlikely, it could occur in the case of unexpected or accidental removal by the administrator. If exploited, an unauthorized user could access data they previously but should no longer have access to.
CVE-2025-9124 1 Rockwellautomation 1 Compact Guardlogix 5370 2026-04-15 N/A
A denial-of-service security issue in the affected product. The security issue stems from a fault occurring when a crafted CIP unconnected explicit message is sent. This can result in a major non-recoverable fault.
CVE-2025-11696 1 Rockwellautomation 1 Studio 5000 Simulation Interface 2026-04-15 N/A
A local server-side request forgery (SSRF) security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to trigger outbound SMB requests, enabling the capture of NTLM hashes.
CVE-2025-11697 1 Rockwellautomation 1 Studio 5000 Simulation Interface 2026-04-15 N/A
A local code execution security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to extract files using path traversal sequences, resulting in execution of scripts with Administrator privileges on system reboot.
CVE-2025-11084 1 Rockwellautomation 1 Factorytalk 2026-04-15 N/A
A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period.
CVE-2024-10944 1 Rockwellautomation 1 Factorytalk Updater 2026-04-15 8.4 High
A Remote Code Execution vulnerability exists in the affected product. The vulnerability requires a high level of permissions and exists due to improper input validation resulting in the possibility of a malicious Updated Agent being deployed.
CVE-2021-22681 1 Rockwellautomation 20 Compact Guardlogix 5370, Compact Guardlogix 5380, Compactlogix 1768 and 17 more 2026-03-06 9.8 Critical
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.
CVE-2025-7025 1 Rockwellautomation 1 Arena 2026-02-26 7.8 High
A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information.
CVE-2025-7032 1 Rockwellautomation 1 Arena 2026-02-26 7.8 High
A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information.