| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| Stored Cross-Site Scripting (CWE-79) in the OPC XML-DA server statistics in Loytec LIP-ME201C, L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.16 on LINX-A64 allows an unauthenticated remote attacker to execute arbitrary JavaScript in an administrator's browser (session hijacking, credential theft, device reconfiguration) via a crafted `User-Agent` header in a `POST /da` request. |
| Improper Privilege Management (CWE-269) in `/usr/bin/ltsudo` in Loytec LIP-ME201C, L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.16 on LINX-A64 allows a `superadmin`-group attacker to reset the password of any LARM user (including the `larmapp` service account) via the `set-passwd` subcommand. |
| Improper Link Resolution (CWE-59) in `/usr/bin/larm_starter` in Loytec L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.16 on LINX-A64 allows an authenticated `larmapp` attacker to make `/etc/passwd` writable by the `larmapp` group (leading to root privilege escalation) via a symlink attack on `/etc/lighttpd/ssl/server.pem`. |
| Improper Authentication (CWE-287) in the PAM configuration in Loytec LIP-ME201C, L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.16 on LINX-A64 allows a local attacker to authenticate as a uid=0 account without a password and obtain a root shell via an `/etc/passwd` entry with an empty password field. |
| Stack-based Buffer Overflow (CWE-121) in `/usr/bin/ltsudo` `cmd_ipaddr_conflict` in Loytec LIP-ME201C, L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.16 on LINX-A64 allows a `superadmin`-group attacker to trigger a SUID-root process abort or potentially elevate privileges via an overly long interface-name argument. |
| Unchecked input for loop condition (CWE-606) in the SNMP agent in Loytec LIP-ME201C, L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.16 on LINX-A64 allows an unauthenticated remote attacker to cause persistent denial of service (CPU exhaustion) via a crafted SNMP GETNEXT request with a large OID component. |
| Out-of-bounds Read (CWE-125) in BACnet packet parsing (`bacdt_datetime_to_tod`) in Loytec LIP-ME201C, L-INX, L-GATE, L-ROC, L-IOB, L-DALI, L-VIS and L-PAD through 8.4.18 on LINX-A64 allows an unauthenticated remote attacker to crash `linx_a64.exe` and ultimately reboot the device via a malformed BACnet TimeSynchronization or UTC-TimeSynchronization packet with an invalid month value. The same vulnerability affects multiple other Loytec products. |
| Exposure of Sensitive Information (CWE-200) in LWEB802 browser `localStorage` in Loytec LWEB-802 before 5.0.8 on all platforms allows an unauthenticated remote attacker to leak stored management credentials via a crafted link. |
| Reflected Cross-Site Scripting (CWE-79) in LWEB802 in Loytec LWEB-802 before 5.0.8 on all platforms allows an unauthenticated remote attacker to execute arbitrary JavaScript in a victim's browser and perform actions with the victim's privileges via a crafted link containing a malicious `project` or `mspParams` parameter. |
| LOYTEC electronics GmbH LINX Configurator (all versions) is vulnerable to Insecure Permissions. An admin credential is passed as a value of URL parameters without encryption, so it allows remote attackers to steal the password and gain full control of Loytec device configuration. |
| LOYTEC electronics GmbH LINX Configurator (all versions) is vulnerable to Insecure Permissions. Cleartext storage of credentials allows remote attackers to disclose admin password and bypass an authentication to login Loytec device. |
| LOYTEC electronics GmbH LINX Configurator (all versions) uses HTTP Basic Authentication, which transmits usernames and passwords in base64-encoded cleartext and allows remote attackers to steal the password and gain full control of Loytec device configuration. |
| LOYTEC LINX-151, LINX-212, LVIS-3ME12-A1, LIOB-586, LIOB-580 V2, LIOB-588, L-INX Configurator devices (all versions) use cleartext HTTP for login. |
| LOYTEC LINX-151, LINX-212, LVIS-3ME12-A1, LIOB-586, LIOB-580 V2, LIOB-588, L-INX Configurator devices (all versions) lack authentication for the preinstalled version of LWEB-802 via an lweb802_pre/ URI. An unauthenticated attacker can edit any project (or create a new project) and control its GUI. |
| LOYTEC LINX-151, LINX-212, LVIS-3ME12-A1, LIOB-586, LIOB-580 V2, LIOB-588, L-INX Configurator devices (all versions) send password-change requests via cleartext HTTP. |
| An Insufficiently Protected Credentials issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The application does not sufficiently protect sensitive information from unauthorized access. |
| An Insufficient Entropy issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The application does not utilize sufficiently random number generation for the web interface authentication mechanism, which could allow remote code execution. |
| A Relative Path Traversal issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The web user interface fails to prevent access to critical files that non administrative users should not have access to, which could allow an attacker to create or modify files or execute arbitrary code. |
| A Cross-site Scripting issue was discovered in LOYTEC LVIS-3ME versions prior to 6.2.0. The web interface lacks proper web request validation, which could allow XSS attacks to occur if an authenticated user of the web interface is tricked into clicking a malicious link. |
| LOYTEC LIP-3ECTB 6.0.1, LINX-100, LVIS-3E100, and LIP-ME201 devices allow remote attackers to read a password-hash backup file via unspecified vectors. |